| ___ 1. |
Egress windows; Minimum size 22"
vertical or horizontal with 5 square feet minimum openable area. Maximum seal height
36" above floor. MHCSS 3280.106 & 3280.404 |
| ___ 2. |
Exits; Two required Single section 12'
minimum distance center to center. Double section 20' minimum center to center. MHCSS
3280.105 |
|
A. One exit within 35' of any bedroom
doorway. |
|
B. Exterior swing door require
28" x 74" clear opening. Sliding glass require 28" x 72" clear
opening. |
| ___ 3. |
Flame Spread; Walls and ceilings adjacent to
or enclosing Furnace or water heaters not to exceed 25 flame spread rating. Combustible
doors shall be covered with a limited combustible material (i.e. 5/16" sheet. rock
min.) Lovers to be of same combustible as door minimum. MHCSS 3280.203 |
| ___ 4. |
Exposed interior finishes; Adjacent to
cooking range not to exceed 50 flame spread. MHCSS 3280.203. |
| ___ 5. |
Vertical clearance above range minimum
24" to combustibles. MHCSS 3280.204(e). |
| ___ 6. |
Smoke detectors; Located on wall between
first bedroom and living room. In hall ways must be between return air and living area.
Shall be attached to house power. |
| ___ 7. |
Solid-fuel-burning stoves/fireplaces; Must
be listed for manufactured housing use and installed to manufactures instructions and
MHCSS 3280.709(g). Note: See ANSI A225.1 Annex D section 4.2, 4.2.1, 4.2.2 and 4.2.3 when
this applies. |
| ___ 8. |
Electrical System; Must be tested for
continuity to confirm proper bonding, test equipment for proper connection and operation,
and test for polarity. MCHSS 3280.810. |
| ___ 9. |
Electrical system properly protected for
required amperage. Aluminum conductors connected to device marked CO/ALR. Exterior
receptacles GFCI protected (exp. Heat tape receptacle). Conductors of dissimilar materials
connected in accordance with NEC 110-14. |
| ___ 10. |
Replacement furnaces and water heaters;
vents, roof jacks, and chimney must be listed for manufacture housing use. |
| ___ 11. |
Furnaces and water heaters must be secured
from displacement and accessible for service or replacement. MHCSS 3280.709(a). |
| ___ 12. |
Fuel burning Furnaces and water heaters must
be installed to provide complete separation of the combustion system from the interior of
home. (Direct vent or outside combustion air required) MHCSS 3280.709(d). |
| ___ 13. |
Water heater floor adequate for water heater
support. |
| ___ 14. |
Roof snow load. # Information acquired by |